Abstract
This paper proposes a new current balancer in singlephase three-wire secondary distribution systems using the correlation coefficients. The components of the load currents correlative to the primary side voltage waveform, which correspond to the active currents, are detected in each feeder, then the nonactive and unbalanced-active components are compensated on the source side. The balanced currents with unity power factor are obtained in each feeder. The basic principle of the proposed method is discussed in detail, and then confirmed by digital computer simulation. A prototype experimental system is constructed and tested. Experimental results demonstrate that the balanced source currents with unity power factor are obtained in spite of unbalanced load currents.
Original language | English |
---|---|
Pages (from-to) | 50-58 |
Number of pages | 9 |
Journal | Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi) |
Volume | 169 |
Issue number | 1 |
DOIs | |
Publication status | Published - Oct 2009 |
Externally published | Yes |
Keywords
- Active current
- Balanced condition
- Correlation coefficient
- Current balancer
- Single-phase three-wire secondary distribution system
- Unbalanced condition
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering